Safety and reliability in any environment
General
The switchgear must be suitable for 36 kV rated voltage and specifically conceived for the
secondary distribution substations in M.V. with either ring or radial type networks.
The switchgear must have the following general features:
• Rated voltage up to 36kV
• Rated current for single functions of 630A
• Available both in compact and modular versions, extensible or not.
• Compact design with up to 5 functions
• Capable of withstanding immersion for 24 hours.
• Availability of reduced height versions
• Easy installation and operation
• Reduced dimensions
• Internal arc containment 16kA 1s, both in live tanks and cable compartment.
• Internal arc proof classification AF and AFL (acc. to IEC 62271-200) as option with
rear or side duct
• Service continuity LSC2A (acc. to IEC 62271-200)
• Simplicity of inspection and maintenance
• Long operational life
• Modularity & Versatility
• Remote operation possible
• External enclosure made of stainless steel AISI 304
• Mechanical interlocks which ensure the exact sequence of operations
• Circuit breaker of vacuum type
• Direct earthing of the switchgear whole structure;
• Total segregation of the live parts, which are contained inside a stainless steel
housing, hermetically sealed and filled with gas SF6;
• Accessibility to the fuses without any danger, with preventive earthing of the two
ends;
• Availability of earthing switches with making capacity;
• Mechanical interlocks, granting the exact sequence of the operations.
The basic units which can be combined together in the modular version are:
• Incoming/outgoing unit with switch disconnector (C)
• Transformer protection unit with fuses (T1)
• Incoming/outgoing unit with circuit-breaker (CB)
• Direct incoming/outgoing unit (R).
It must be also be possible to further extend the configurations by externally connecting
with purposed bus-bars several basic units the one to the other, provided that they were
initially bought in the extensible version.
The switchgear consists of a stainless steel metal housing, suitably welded in order to
assure the sealing of the gas SF6.
The switchgear must fully comply with the IEC 62271-100, IEC 62271-200 and IEC 60694
Standards.
The following Degree of protection against accidental contact and ingress of foreign
objects must be assured:
Main electric circuits | IP67 |
Fuses compartment | IP3X |
Operating mechanisms | IP2XC |
Cables connection compartment | IP2XC |
Common:
Rated voltage | Ur[kV] | 36 |
---|---|---|
Rated power frequency withstand voltage (50/60 Hz 1 min.): towards the ground and between phases across the isolating distance | Ud[kV] | a) 70 b) 80 |
Rated lightning impulse withstand voltage: a) towards the ground and between phases b) across the isolating distance |
Up[kV] | a) 170 b) 195 |
Internal arc withstand current 1 s | [kA] | 16 / 20 |
Continuity of service | LSC2A (according to IEC 62271 – 200) | |
Rated current | Ir[A] | 630 |
Breaking capacity of active circuits (cos. ϕ 0.7) and ring circuits at 0.3 Vn | I1-I2a[A] | 630 |
Breaking capacity of no-load transformers | I3[A] | 25 |
Breaking capacity of no-load lines/cables | I4a-I4b[A] | 25 |
Short time withstand current 1 s on main circuits and earth circuits | Ik[kA] | 16/20/25 |
Switch disconnector making capacity and earthing switch making capacity | Ima[kA] | 40/50/62.5 |
Water proof test 0,3 bar | [kV] | 70 kV x 1 min. – Vn x 24 hours |
Electrical life test | 100 operations CO at 630 A | |
Rated filling pressure Pme3) | 130 kPa (absolute at 20 °C) | |
Ambient temperature | -25°C/+40 °C |
Transformer protection unit with fuses:
Transfer current | I4[A] | 800 |
Normal current of the fuse | [A] | 63 |
Short circuit making current | [kA] | 78.75 |
Short circuit breaking current | [kA] | 31.5 |
Short time current on earthing switch downstream of fuses | Ik[kA] | - |
Circuit-breaker unit:
Breaking capacity of Circuit-Breaker | [kA] | 16/25 |
Circuit-Breaker rated switching sequence | O - 0,3 s - CO - 3 min CO - 3 min - CO |
|
Number of mechanical operations of switch disconnector and earthing switch | n | 1000 |
Number of mechanical operations of Circuit-Breaker | n | 2000 |
Modular version
C Unit
The line unit (C) consists of a switch-disconnector and an earthing switch.
The switch-disconnector, consists of three poles mounted on a steel structure and
connected to a common shaft, which, on its turn, is connected to the operating
mechanism. The pole consists of an upper part and of a lower one, in epoxy resin. The
upper part houses the fixed contacts and the connection to the bus-bars, while the lower
part houses the sliding contacts, the moving contacts and the piston for the blowing
action.
The control can be either manual or motorized (upon request). In the manual control, the
only possible action is performed by means of the purposed operating lever supplied in
the delivery, while in the motorized control the operation can be executed either by local
or by remote control.
T1 Unit
The transformer protection unit consists of a switch-disconnector and an earthing switch,
equal to those present in the line unit. Besides, three fuses, having dimensions complying
with the DIN Standards, are installed.
Every fuse is inserted inside a fuse-holder, from which it can be frontally extracted after
having opened the protection dust proof enclosure. The insulation between fuse and fuseholder
is of the solid-air type. The fuse-holders, manufactured in epoxy resin, are tight.
Positioned the one on the other inside the switchgear hermetic housing, they are fully
immerged in the gas SF6. The fuses’ position assures an easy replacement and a sure
intervention by means of the striker. The extraction of a fuse is possible only if the same
one is isolated and earthed both on the supply side and on the opposite one. A device
makes the automatic opening of the switch disconnector when one or more fuses get
blown; such device is actuated by the fuse striker. On the fuses protection dust proof
enclosure, the mechanical signalling of blown fuse is foreseen
The fuse rated current depends on the transformer power.
The fuse rated current depends on the following characteristics:
• service voltage,
• transformer power.
The installed fuses must comply with the IEC 60282-1 Standards and be dimensioned
according with the DIN 43625 Standards. When the elimination of a fault corresponds to
the blowing of either one or two fuses, it is recommended to replace all the three of them
KJC1200
CB Unit
The CB unit consists of a vacuum circuit-breaker connected in series with a three position
disconnectors.
The disconnector’s positions are:
a - service position
b - neutral position
c earthed
The operations of the disconnector are only possible provided that the circuit-breaker is
open.
The circuit-breaker operating mechanism is of mechanical type, with energy accumulation
and trip-free. It can be customized with a wide range of accessories, to be easily and
quickly installed on a purposed accessory plate.
Such plate, realized in a single block and positioned on the circuit-breaker front side,
allows to easily dismount/mount the accessories, so facilitating the possible replacement
or maintenance interventions.
Upon request, the circuit-breaker unit can be equipped with a protection relay.
Riser Unit
The riser unit is used to translate in safety conditions a line from a point situated at a
certain height to another point having a different height.
Safety
In order to grant the operator’s safety and to prevent the risk of wrong operations, the
switchgear is equipped with the following safety devices:
• controls and fuses protective boxes, which protect the operator from the moving
parts and from the auxiliary voltages present inside;
• lower protective boxes, for protecting the cables and the bushings;
• pressure relief valves, installed in the lower part of the stainless steel housing,
which assure the gas flow-off in case of a possible "internal arc", without causing
breaks on the front part, where the personnel charged with the electric operations
could be possibly operating.
Besides these basic features, these additional safety devices are provided:
• key lock (optional), for preventing wrong operations when using the apparatus
• door interlock device, allowing to open the switchgear protective boxes only when
the earthing switch is positioned on "closed earth";
• interlock on the fuse-holder cover, preventing to place the cover itself on the fuseholder
when the fuse is not mounted inside it, so preventing to put the apparatus
into service
• device on the fuses compartment door, signalling the fuse blown condition through
a coloured indicator (white for fuse ok, red for fuse blown) and preventing the door
itself to get closed when it was opened by blown fuse;
• interlock device on the operation of the disconnector control in the motorized
switchgear, providing to cut out the power supply to the gear motor, so preventing
its electric movement, in case the manual operating lever would get inserted
• mechanical interlocks which prevent any wrong operation, so granting the utmost
safety for the operator.
The interlocks are the following ones:
• interlock between switch-disconnector and earthing switch. It prevents the earthing
switch to get closed when the switch-disconnector is closed. In the same way, the
switch-disconnector closing operation is prevented when the earthing switch is
closed;
• interlock between circuit-breaker and disconnector in the CB unit. When the
interlock is shifted to the left, the circuit-breaker closing is prevented. When the
interlock is shifted to the right, the disconnector operation is prevented;
• interlock between disconnector of the transformer protection unit and fuses
compartment door. It prevents the opening of the fuses compartment door when
the switch-disconnector is on closed position and the earthing switch is on open
position
Switchgear
Using modular version, the switchgear is composed putting one close to the other the
modules, which are connected on top by means of suitable busbars. Busbars must be
able to carry 1250A.
Compact Version
In the compact version, the required functions are contained within the same SF6
compartment.
For all the switchgear, the maximum allowed depth is 1072mm. The maximum allowed
height is 1720mm (extension bushings excluded).
The following switchgear must be available:
C-C-C max width 1200mm
C-C-C-C max witdh 1550mm
C-CB max width 930mm
CB-CB-CB max width 1670
C-C-CB max width 1280mm
C-CB-CB max width mm 1490
C-C-CB-CB max width mm 1840
CB-R max width mm 930
CB-C-R max width mm 1280
CB-C-C-C max width mm 1630
CB-C-C-R max width mm 1630
T1-C max width 930mm
T1-R max width 930mm
T1-C-R max width 1280mm
T1-C-C max width 1280mm
T1-C-C-C max width 1630mm
T1-C-C-C-C max width 1980mm
T1-T1-C-C-C max width 2200mm