8DJH 36KV

8DJH 36KV

Gas-insulated switchgear 8DJH 36

Maintenance-free for lifetime

 

Description

Gas-insulated switchgear 8DJH 36
8DJH 36

              Up to 36 kV

  • Up to 20 kA

  • Up to 630 A

  • Single busbar

  • Type-tested

  • Metal-enclosed

  • Climate-independent

  • Maintenance-free

  • Individual panels and block versions

  • No gas work at site

  • Fast and easy to install

Technical Data

Rated voltage

kV

36

Rated short-duration power-frequency 
withstand voltage

kV

70

Rated lightning impulse withstand voltage

kV

170

Rated frequency

Hz

50/60

Rated normal current of busbar

A

630

Rated normal current of feeder

A

≤ 630

Rated short-time withstand current, 3 s

kA

≤ 20

Rated peak withstand current

kA

≤ 50/52

Rated short-circuit making current

kA

≤ 50/52

Design and construction

 

Partition Class:

PM (partition of metal)

Loss of service continuity category for 
panels or panel blocks: 
- Panels with disconnector (R, T, L) 
- Panels without disconnector (K, M)

 
 
LSC 2 
LSC 1

Accessibility of Compartments (enclosure): 
- Busbar compartment: 
- Switching-device compartment: 
- Low-voltage compartment (option): 
- Cable compartment for panels or panel blocks 
with HV HRC fuses (T) 
without HV HRC fuses (R)

  
Non-accessible 
Non-accessible 
Tool-based 
  
Interlock-controlled 
Interlock-controlled

Internal arc classification (option)

 

Designation of the internal 
arc classification, IAC 
IAC class for 
- Wall-standing arrangement 
- Free-standing arrangement

Rated voltage is 36 kV 
 
 
IAC A FL to 20 kA 1s
IAC A FLR to 20 kA 1s

Type of accessibility A 

 
 
- F 
- L 
- R

Switchgear in closed electrical 
service location, access "for 
authorized personnel only" 
(according to IEC 62271-200) 
Front 
Lateral 
Rear (for free-standing arrangement)

Arc test current

Up to 20 kA

Test duration

1 s